Turner's Home Page Turner's Product Line Delta-Star Switches Engineering Center Typical Specifications Installation Help
Customer ServiceSite Search Contacts
OperatorsPhase-Over-PhaseVertical Break InterruptersCenter Break
Installation Help

HYDRAULIC OPERATOR HS-2

(product obsoleted in early 2004)

View Online

  • Receiving Instructions
  • Operation
  • Operator Mechanical Installation
  • Open / Close Cycle Descriptions - (Separate Page)
  • Troubleshooting

    Download File

  • Download PDF File
  • RECEIVING INSTRUCTIONS

    Handle with extreme care.

    Please read the following instructions completely prior to commencing installation.
    The equipment is a precision-engineered motor operator.
    Every effort has been made to properly prepare the equipment for shipment. To lift operator out of crate, attach rigging to the top of the aluminum support channel.

    Carefully and thoroughly inspect this shipment.

    It is absolutely necessary that any and all shipping loss or damage is reported to the local freight agent within fifteen (15) days of delivery. Please request an on-site agent inspection of the damages.

    NOTE:
    Failure to file a damage/loss claim within the specified period waives the right to supplier or carrier loss reimbursement. Do not accept damaged goods until the delivering driver has made a damage notation on the freight bill.

    These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchasers purposes, the matter should be referred direct to the Turner Electric, LLC factory at 618-397-1865.

    DESCRIPTION

    The Turner Hydraulic Actuated Motor Operator (HAMO) model HS-2 is a variable speed, variable torque operator for use with airbreak disconnect switches. The modular unit can be utilized to operate a switch from remote locations and for automatic relay switching schemes.

    OPERATION

    The HS-2 power unit consist of a motor driven hydraulic pump, and manifold with restrictor valves and solenoid actuated valves. When activated, the pump builds fluid pressure to a specified pressure against a stored energy accumulator. When adequate pressure is obtained, a pressure sensitive switch energizes the close or open solenoid driven valves, allowing fluid to flow in the appropriate direction.

    The switch operating speed is fully adjustable in the field. The three (3) cartridge valves located on the power unit manifold (see Fig. 1) control the fluid and therefore the speed of rotation as well as the torque output.

    IMPORTANT:
    Regardless if unit is installed on a new or existing switch, the disconnect switch should be completely and properly adjusted and operating satisfactorily prior to motor operator installation. If an existing switch, proper maintenance should be performed.

    OPERATOR MECHANICAL INSTALLATION

    NOTE: Use the aluminum support channel for lifting the motor operator.

    HS-2 TROUBLESHOOTING

    PROBLEM: Everything dead -- no red or green indicator lamp.

      1) Replace fuse 2

    PROBLEM: Have indicator lights but motor relay only clicks.

      1) Battery voltage possibly low

      2) Replace fuse 1

    PROBLEM: Pump motor running but slight or no pressure build up.

      1) Low on oil - fill to top of site glass

      2) Defective pump - replace

      3) Defective accumulator - replace

    PROBLEM: Pressure builds to 1200 psi or above, but actuator does not rotate.

      1) Low batteries - voltage below pickup of start relay

      2) Defective start relay - replace

      3) Defective pressure switch - replace

      4) Respective open/close valve:

        a) May be sticking

        b) Coil may not be closing

        c) Check resistors on 125 VDC units

      5) Speed adjustment valves closed - open and adjust

    PROBLEM: Operator starts to open or close then stops -- oil pressure keeps on building.

      1)Check limit switches - defective or need adjustment

      2) Defective open or close relays - replace

      3) Open and close relay closing at same time - check wiring

    PROBLEM: Operator opens or closes without pressure build up.

      1) Accumulator over charged - not to exceed 825 psi

      2) Pressure switch defective or misadjusted - replace - readjust

      3) Respective open/close valves stick - open - remove and check - replace if defective.

    PROBLEM: Operator not shutting off at end of cycle.

      1) LS1 or LS2 defective or out of adjustment

      2) Respective relay holding on - replace

    PROBLEM: No fast close.

      1) Defective or out of adjustment LS3

      2) No accumulator charge -- pressure gauge should read 825 psi immediately after pump starts then build to 1200 psi. Read on shut down.

      3) Fast close valve:

        a) May be sticking

        b) Coil may not be closing

        c) Respective resistors on 125 VDC unit may be open

      4) Slow close adjustment valve open too far, using too much fluid - restrict

      5) Fast close adjustment valve not open enough

      6) Accumulator overcharged - not to exceed 825 psi (should have minimum pressure differential of 375 psi between pre-charge and pressure switch setting)

      7) Unit low on oil

    PROBLEM: Pressure gauge will build to 1200 psi then drop to "0" then back to pre-charge and above.

      1) Not enough pressure differential between pre-charge and pressure switch setting - re-set pressure switch, replace accumulator.

      2) Excessive oil in accumulator, giving false reading to pressure switch - remove accumulator and drain excessive oil before adding nitrogen. Normally we to low precharge. Replace accumulator.

      3) Slow-close or open adjustment valve open too wide.

    PROBLEM: Actuator has jerky start - stop reaction.

      1) Start relay is defective - replace

      2) Pressure switch defective - replace

      3) Manual handle assembly riding on top drip shield plate. Raise assembly off drip shield one (1") inch.

    PROBLEM: Pressure builds slowly, pressure gauge does not jump to 825 psi on start.

      1) Accumulator has no gas pressure - replace
      Note: When charging accumulator, always remove remaining gas/oil before re-charging. Consult factory for pre-charge kit.
    RECOMMENDED SPARE PARTS
    FOR 1-3FOR 4-10
    DESCRIPTIONUNITSUNITS
    Open/Fast close cartridge valve24
    Open/Slow close solenoid valve12
    Slow close cartridge valve12
    Solenoid23
    Fast close solenoid valve12
    Time delay relay12
    Motor relay02
    Start relay12
    Open relay12
    Close relay12
    100 Watt heater strip13
    Accumulator01
    Limit switch13
    Pressure switch01
    Power Units (complete)01

    Products Delta-Star Switches Engineering Center Typical Specifications Installation Help Customer Service Site Search Contacts

    ©2001-06 Turner Electric, LLC. : Last updated: Nov 05